70
Figure 15-1-3 Log setting
16 Calibration of tool/workpiece
16.1 Base coordinate three-point calibration
Operation procedure
1. In the menu, select Put into operation→Measure→User part calibration.
2. Select the user workpiece number to be calibrated, and set the user workpiece name.
3. Click the [Start Calibration] button.
4. Move to the origin of the base coordinates and click [Origin] to obtain the origin coordinates of
the coordinate record.
5. Move to a point in the X direction of the calibration base coordinate, and click [X direction] to
obtain the coordinate record coordinates.