Manual 35086
ProTech-GII with Math Functions
Woodward
96
The “Up Arrow” and “Down Arrow” keys are used to highlight the desired page. The ENTER key selects
the page.
Configure Menu Page Descriptions
Display:
This page is used to set the language, the display action when a trip occurs, the Home
page and the display filter time.
Speed
: This page is used to configure the local Speed, Acceleration, Start Logic, Speed
Redundancy, and Acceleration Redundancy settings.
Trip Latch
: This page is used to configure the local Trip Latch function.
Alarm Latch
: This page is used to configure the local Alarm Latch function.
Dedicated Discrete Inputs:
This page is used to configure the Reset, Start, and Speed Fail
Override input sharing.
Test Modes
: This page is used to configure the local Test Routines.
Auto-Sequence Test
: This page is used to configure the Auto-Sequence Test Routine. This routine
can only be configured from Module A.
Modbus
: This page is used to configure the local Modbus communication link.
Power Supply Alarms
: This page is used to configure the local power supply alarm logic.
Configuration Management Menu
: This page is used to view the configuration CRCs, configure the
module-to-module configuration comparison function, and to use the module-to-module configuration
copy function.
Password Change Menu
: This page is used to set the Test Level Password and Config Level
Password.
Configuration Procedure
1. Module must be in a “tripped” state to make any configuration changes.
2. Select the “Config Menu” soft key.
3. Use the Up / Down Arrow keys to select the desired category and press the ENTER key to select.
4. Use the Up / Down Arrow keys to scroll to desired parameter setting then press the ENTER key to
select.
5. If the module is not in the “Configuration” mode, the password entry screen will appear. Enter the
configuration level password then press the ENTER key. See the password section of this manual
for information on entering a password.
6. The screen is now in edit mode. Using the soft keys, edit the desired value:
a. Use the "Cursor Left" key to move to the left.
b. Use the "Value Down" or "Value Up" keys to change the highlighted value.
c. Use the "Cursor Right" key to move to the right.
d. Use "Select Left" or "Select Right" to select a different option.
7. Use the front panel Up / Down Arrow keys and ESC / ENTER keys to navigate within all Config
Menu pages to configure desired parameter settings.
8. After all desired parameters have been configured; press the HOME key to exit Configure Mode.
9. If any parameters were changed, the module will display the “Save Configuration” screen (refer to
below figure). At this point the user can press the respective soft button to choose the desired action:
a.
Save
: This action saves any configuration changes, exits Configuration Mode, then displays the
Home screen.
b.
Discard:
This action does not save any configuration changes, exits Configuration Mode, then
displays the Home screen.
Released