Manual 35086
ProTech-GII with Math Functions
Woodward
109
The overall CRC value is shown in the upper left corner of the Configuration Overview page and can be
different between modules as it encompasses the entire configuration, including settings that are
expected to be different between modules. See exclusion details in the “Configure Compare/Copy
Exclusions” section below.
Comparing CRCs between modules before and after a settings change can provide confirmation on
where configurations are the same and to facilitate isolation of configuration changes.
Note that passwords are not included in the configuration and are therefore not compared or copied
between modules.
For additional details on the values displayed on this screen, refer to the Configuration Overview screen
section of the Programming and Configuration Tool (PCT) Chapter.
Configure Compare/Copy Exclusions
The Configuration Compare and Configuration Copy functions intentionally exclude settings that are
expected to vary from module to module. Therefore, when executing a Configuration Copy, these settings
are not included in the copy and, likewise, the settings are ignored during the Configuration Compare.
The excluded settings are listed below.
The excluded settings are:
Passwords
Display settings
o
Home Screen
o
Jump to Home Screen on Trip
o
Selected Language
o
Speed Filter Tau
Modbus Slave Address
Configure Configuration Compare Page
Figure 5-23. Configuration Compare Screen Example
This page is used to configure the Configuration Compare function.
Configuration Compare:
Used to enable or disable the module-to-module Configuration Mismatch
alarm. When enabled, this function compares the configuration of the current module against the
other modules and generates an alarm if there is a difference. Valid values: USED or NOT USED.
Note:
If each of the modules is deliberately configured differently to meet a specific application’s
requirements, this setting should be set to “NOT USED”.