Manual 35086
ProTech-GII with Math Functions
Woodward
52
Figure 3-2. Module Diagram with Speed Redundancy Manager Configured
Security
The ProTech-GII utilizes two password levels, a Test Level Password and a Config Level Password. The
same passwords are used by the Programming and Configuration Tool (PCT) and Front Panel.
The Test Level Password is required to:
Initiate
tests.
Reset logs (except for the Peak Speed/Acceleration Log).
Change the Test Level Password.
Copy the configuration to another module.
The Config Level Password provides access to any function that requires the Test Level Password.
Additionally, the Config Level Password is required to:
Change any program setting.
Upload the Settings File into a module using the PCT.
Reset the Peak Speed/Acceleration Log.
Change the Config Level Password.
Each of these passwords meets NERC (North American Electric Reliability Corporation) cyber security
requirements.
The default password for Test and Config Level is “AAAAAA”.
Module-to-Module Communications
An isolated communications bus is used between modules to:
Share module input signals and event latch status information.
Copy configuration settings from one module to another module.
Compare module configuration settings for differences.
Verify the health and state of the other modules before allowing a module test to be performed.
Pass a “module test token” between modules when performing an “Auto Sequence Test” routine.
Released