Manual 35086
ProTech-GII with Math Functions
Woodward
90
Monitor System Status Page
Figure 4-25. Monitor System Status
This page provides users the health status of all modules.
Unit Health Unknown
: This message indicates the status of the module is unknown due to one of
the following reasons:
o
A module not properly installed
o
A module to module network communication failure
o
A front panel communication failure.
Unit Health OK
: This message indicates the module is operating properly.
Unit Health Bad
: This message indicates an internal module alarm is present due to one of the
following reasons and should be repaired or replaced:
o
Module processor failure
o
Module memory failure
o
Module data bus failure
Module Information Page
Figure 4-26. Monitor Module Information
This page displays the module’s coded identification.
Product ID
: Indicates the module hardware model.
Module S/N
: Indicates the module hardware serial number.
Released