Manual 35086
ProTech-GII with Math Functions
Woodward
94
Chapter 5.
Configuration Using the Front Panel
Introduction
Users can configure the ProTech-GII using the following methods:
1. Configure each module separately via the front panel keypad.
2. Configure one module via the front panel keypad then copy that configuration to the remaining
modules with the “Copy Configuration” option on the “Configuration Management Menu” screen.
3. Use the provided Programming and Configuration Tool (PCT) software program to create a Settings
File, connect to a module and upload the file to that module. Then, configure the remaining modules
by repeating the connect and upload method or by using the “Copy Configuration” option on the
“Configuration Management Menu” screen method.
For safety purposes, a module must be in a “tripped” state to allow any configuration settings to be
changed or uploaded.
Changing the configuration settings in the ProTech-GII is permissible
only when the unit is in a trip condition. If the unit is not in a trip
condition, configuration changes are inhibited. If no trip condition is
present, the configuration save will ask if a trip is desired. A trip will
only be allowed if the other modules are not tripped.
The changes that can be made via the front panel are limited to the following functions.
Table 5-1. Front Panel Functions that Can Be Modified
Display Settings
Acceleration settings
Trip Latch settings
Language
Selection
Acceleration Trip Enabled
Energize/De-energize to Trip
Home Screen on Trip Option
Accel Trip Enable Speed
Latching/Non-Latching
Home
Screen
selection
Accel Trip Threshold [RPM/s]
Trip is Alarm [No/Yes]
Displayed Speed Filter
Acceleration
Filter
Alarm Latch settings
Speed Input Settings
Start Logic settings
Start Input Sharing
Speed Probe Type
Speed Fail settings
Reset Input Sharing
Number of Gear Teeth
Speed Fail Timeout settings
Speed Fail Override Input Sharing
Gear
Ratio
Speed Redundancy Manager
Analog Output (Speed) settings
Overspeed Trip Setpoint [RPM]
Input
Selections
Test Mode settings
Sudden Speed Loss Action
Function
selections
Auto-Sequence Test settings
Speed Loss Threshold [RPM]
Difference alarm settings
Modbus Communication settings
Password Change
Acceleration Redundancy
Manager
Power Supply 1 & 2 Alarms
[No/Yes]
Test Level Password
Input
Selections
Configuration Management
Config Level Password
Function
selections
Overview
Compare
feature
Copy
feature
Released