Manual 35086
ProTech-GII with Math Functions
Woodward
107
Configure Modbus Page
Figure 5-19. Configure Modbus Screen Example
This page is used to configure the module Modbus communications port.
Mode:
Used to select the serial communication mode to use for serial communications port. Valid
values: RS232 or RS485
Baud Rate:
Used to set the serial data rate for the serial communications port. Valid values: 19200,
38400, 57600, or 115200 bits/s.
Communication Parity:
Used to set the parity value for the serial communications port. Valid
values: NO PARITY, EVEN PARITY, or ODD PARITY
Slave Address:
Used to set the unique slave address for the serial communications port. If all three
modules are connected to the same network, each will require a unique address. Valid values: 1-247
Enable Write Commands:
Used to enable (accept) or disable (ignore) Modbus “Write” commands
(e.g., Reset command, Initiate Auto Simulated Speed Test command). See Monitor and Control
Section in the Modbus Chapter for more information. When this setting is set to “NO”, the serial
Modbus communication port can only be used for monitoring values. Valid values: Yes or No
Configure Power Supply Alarms Page
Figure 5-20. Configure Power Supply Alarms Screen Example
This page is used to enable or disable the power supply input failed alarms.
Enable Power Supply 1 Alarm:
Used to enable or disable the Power Supply 1 Fault alarm. Valid
values: YES or NO
Released