155
Error Messages
Configuration Error
Figure 8-8. Configuration Error window
The configuration check is performed by the ProTech-GII when a Settings File is loaded to a module. If
there is an error, the settings are not changed and the “Configuration Error Log” must be reviewed. Note
that the PCT must be connected to the module to see the log.
Note:
Since the “Configuration Error Log” is stored in the module volatile memory, the log is cleared
when the module is powered off.
Data Entry Error
When editing an existing Settings File, or modifying the settings currently loaded in a module, an error
window is displayed if data entered is invalid, incomplete, or out of range, as shown in the example
below.
Figure 8-9. Data Entry Range Error Example
4
Text: Error
–
<block identifier>
configuration contains data that is invalid (out-of-range).
Condition:
A setting has been detected that is out of the range. This error condition needs to be
corrected in the PCT and should be reported to Woodward for correction.