Manual 35086
ProTech-GII with Math Functions
Woodward
159
The resulting scaled value for the specified register will be the raw signal multiplied by a scale factor. The
scale factor values are indicated in the description as “(x 0.01)”, “(x 0.1)”, “(x 10)”, or “(x 100)”.
Last Trip time and date indication (3:0086 – 3:0092)
Last Trip Date/Time represents the Date/Time of the most recent first out trip. The Last Trip time and date
indication registers (3:0086 to 3:0092) are provided for use as a way to time-stamp when a trip condition
occurs. With this logic, when a trip condition occurs, the first-sensed trip condition will be indicated by one
of the registers (1:0038 to 1:0074) changing to a true state. When one of the registers changes to a true
state, the Last Trip time and date indication registers (3:0086 to 3:0092) will indicate the sensed date and
time of the event. This Date/Time will remain locked in these registers until the next trip condition occurs.
Unit Health indication (3:0093)
This register indicates the state of the internal fault trip (if known) as follows:
0 = internal fault trip is TRUE (Unit Health LED is red)
1 = internal fault trip is FALSE (Unit Health LED is green)
2 = state of the internal fault trip is unknown because of a communication fault (Unit Health LED is off)
Auto-Sequence Test Status (3:0094)
This register indicates the state of the Auto Sequence Test as follows:
0 = Not Started
1 = Running
2 = Passed
3 = Failed
4 = Not Completed
Boolean Write Table
Below is the list of discretes available to write.
Table 9-4. Boolean Write Addresses (Code 05)
ADDRESS DESCRIPTION
0:0001 Reset
0:0101
Confirm Auto Simulated Speed Test
0:0102
Initiate Auto Simulated Speed Test
0:0103
Abort Auto Simulated Speed Test
Boolean Read Table
Below is the list of discretes available to read.
Table 9-5. Boolean Read Addresses (Code 02)
ADDRESS DESCRIPTION
1:0001
Over Speed Trip
1:0002
Over Accel Trip
1:0003
Speed Redundancy Manager Trip
1:0004
Speed Probe Open Wire Trip
1:0005
Speed Lost Trip
1:0006
Speed Fail Trip
1:0007
Speed Fail Timeout Trip
1:0008
Resettable Trip Input Trip
1:0009
Internal Fault Trip
1:0010
Power Up Trip
1:0011
Configuration Trip
1:0012
Parameter Error Trip
Released