Process data
CombEfficiency
Man Var O2Ctrl
State O2Ctrl
Air-Related Load
Diag Reg State
Load controller
Controller parameters
ContrlParamList
StandardParam
P Part (Xp)
[15 %]
I Part (Tn)
[320 s]
D Part (Tv)
[40 s]
MinActuatorStep
[1 %]
SW_FilterTmeCon
[3 s]
SetpointW1
SetpointW2
Sd_ModOn
[1 %]
Sd_ModOff
[10 %]
Sd_Stage1On
[-2 %]
Sd_Stage1Off
[10 %]
Sd_Stage2Off
[8 %]
Sd_Stage3Off
[6 %]
ThreshStage2On
[300]
ThreshStage3On
[600]
TempLimiter
(2
TL_ThreshOff
[95 °C]
TL_SD_On
[-5 %]
Cold start
ColdStartOn
(2
[deactivated]
ThresholdOn
(2
[20 %]
StageLoad
(2
[15 %]
StageSetp_Mod
(2
[5 %]
StageSetp_Stage
(2
[5 %]
MaxTmeMod
(2
[3 min]
MaxTmeStage
(2
[3 min]
ThresholdOff
(2
[80 %]
AdditionalSens
(2
[deactivated]
Temp. ColdStart
SetpAddSensor
(2
Release Stages
(2
[Release]
Configuration
LC_OptgMode
[Int LR]
Sensor Select
(2
[Pt100]
MeasureRangePtNi
(2
[150 °C / 302 °F]
var.RangePtNi
(2
[850 °C]
Ext Inp X61 U/I
(2
[0 … 10 V]
MRange TempSens
(2
[90 °C]
MRange PressSens
(2
[2 bar]
Ext Inp X62 U/I
(2
[4 … 20 mA]
Ext MinSetpoint
(2
[0 %]
Ext MaxSetpoint
(2
[60 %]
(1
W-FM 200 only
(2
only with HE password