Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
3 Product description
83054802 1/2018-07 La
34-228
3.3.22 Fuel Meter
FE
0
Pulse-In
Usensor
2
3
X71
4
1
GAS
2 wire
3 wire
FE
0
Pulse-In
Usensor
2
3
X72
4
1
OI
L
2 wire
3 wire
It is possible to connect 2 fuel meters to the W-FM 200:
Gas meter: X71
Oil meter: X72
Supply (PIN 1)
approx. 10 V DC / max 45 mA
Input (PIN 2)
max 10 V DC
High level: min 3 V DC
Low level: max 1.5 V DC
Sensor
Inductive sensor to DIN 19234 (Namur)
Open Collector (pnp)
Reed contact
Frequency
max 300 Hz
The number of impulses per unit of volume must be set in parameter
Pulse-
Value…
.
3.3.23 Flue gas temperature sensor
2
3
X8
6
1
Pt/
Ni 1
000
FU
E
L GA
S
Pt/
Ni 1
000
The flue gas temperature sensor is connected to the O
2
module input X86 (access-
ory).
The sensor has to be configured in parameter
FlueGasTempSens
Alternatively, the flue gas temperature sensor can be used as FGR temperature
sensor (flue gas recirculation). In parameter
FGR sensor X86PtNi1000
must then be defined as FGR temperature sensor [ch. 6.15.3].
3.3.24 Combustion air sensor / CO resistance circuit board
2
3
X87
1
Pt/
Ni 1
000
COM
B
US
-
TI
O
N. AI
R
Pt/
Ni 1
000
2
3
X87
1
Pt/
Ni 1
000
COM
B
US
-
TI
O
N. AI
R
Pt/
Ni 1
000
C
Ox >max
The combustion air temperature sensor is connected to the O
2
module input X87
(accessory).
The sensor has to be configured in parameter
SupAirTempSens
In conjunction with CO control, a resistance circuit board is connected to input
X87. The digital output 3 of the CO measurement amplifier is connected to the O
2
module via the resistance circuit board. The combustion air sensor then has to be
connected to input X60:3/4 [ch. 3.3.20].