Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
54-228
6.1.2 Display
The ABE is equipped with a 4 line display with 16 characters per line. The dial
knob is used to scroll through the display, the cursor
1
indicates the position se-
lected.
1
Normal operation
Status/Reset
Fault history
Lockout history
Operating display
Normal operation
Status/Reset
Fault history
Lockout history
The [info] key is used to jump from any menu level to the
operating display menu. The [esc] key is used to return the
display to the menu point previously used.
Menu level 1
Operating display
Operation
Manual operation
Param & Display
The [esc] key is used to leave any position and to go back
all the way to menu level 1 [ch. 6.3].
Fault display
During a fault condition, the display alternately shows the shutdown behaviour and
the fault diagnosed as a plain text display.
Lockout
Air pressure is
off
The combustion manager is in lockout. Once the fault has
been rectified, the combustion manager has to be reset for
restart [ch. 9.1].
Safety
shutdown
Safety loop
is open
The combustion manager initiates a safety shutdown.
The burner restarts automatically once the fault condition
has been rectified.