Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
7 Commissioning
83054802 1/2018-07 La
174-228
6. Pre-set points
Set
ProgramStop
to
deactivated
.
Use [esc] key to return to the display
SpecialPositions
.
Select
CurveParams
and
CurveSet
.
Select
Actuator positions With Start
.
Do not start switch-off points
AS2
and
AS3
, as this can lead to a deficiency of
air.
7. Preset operating point BS1
Select
BS1
with [ENTER].
The burner drives to operating point BS1.
Check combustion values and, if necessary, adjust via air damper setting (
Air
).
Exit BS1 using [esc] key and save with [ENTER].
8. Preset switch-on point ES2
Select
ES2
.
Set excess air (O
2
content approx. 7 %) whilst observing flame stability.
For two stage burners only
Two stage burners do not have a switch-on point ES3 and no operating point BS3.
Operating point BS2 is full load and should be adjusted as full loaf point BS3 (full
load).
9. Pre-set operating point BS2
Select
BS2
.
Valve for nozzle 2 opens.
Check combustion values and, if necessary, adjust via air damper setting (
Air
).
10. Pre-set switch-on point ES3
Select
ES3
.
Set excess air (O
2
content approx. 7 %) whilst observing flame stability.
11. Adjust operating point BS3 (full load)
Select
BS3
.
Valve for nozzle 3 opens.
Determine oil throughput and if necessary adjust pump pressure.
Check combustion values
Determine combustion limit and set excess air [ch. 7.9].
Use [esc] key to return to the display
CurveSet
.
The pump pressure must not be altered once this work has been completed.