Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
103-228
Standardisation
Select
O2 Control
and confirm with [Enter].
Select load point using dial knob and confirm with [ENTER] key.
Burner drives to load point.
Once the O
2
content has stabilised confirm with [ENTER].
Turn dial knob to the right.
The air-determining actuators drive open on the compound curve, reduce the air
quantity and thus the O
2
content.
Confirm standardised value with [ENTER].
Exit entry using [esc] and save with [ENTER].
Carry out standardisation in all points, point 2 to full load.
Operating mode
O2 trim
O2 monitor
Control parameters
Point: 2 25.0%
O2 compound:XXXX
O2 setpoint:XXXX
Standard val:XXXX
Point: 9 100%
O2 compound:XXXX
O2 setpoint:XXXX
Standard val:XXXX
Point: 9
O2 compound: 3.8
If value is stable
continue w ENTER
Point: 9
O2 compound: 3.8
O2 setpoint: 3.8
Standard val:XXXX
Point: 9
O2 compound: 3.8
O2 setpoint: 1.7
Standard val:10.2
Point: 9
O2 compound: 3.8
O2 setpoint: 1.7
Standard val:10.2
Save
point->ENTER
cancel->ESC
Delay time
is measured
O2 actual value : 2.6
Point: 9 100%
O2 compound: 3.8
O2 setpoint: 1.7
Standard val:10.2
Measurement
successful control
param determined
Continue w ESC
(1
(1
(1
Measurement of delay time (time constant Tau) only at 100 % and in the load point defined under
LowFireAd-
aptPtNo
.
If the measurement fails in the defined load point, select the next higher load point [ch. 6.10.4].
Avoid changing the load points in menu
CurveParams
once standardisation has
been completed. If a load point is changed, the standardisation in this point is de-
leted and O
2
trim is no longer possible. In this case the standardisation for this load
point has to be repeated.