Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
4 Installation
83054802 1/2018-07 La
47-228
Installation position
Install the sensor as close as possible to the flue gas outlet of the boiler, but at
least at a distance of 1 x Ø of the flue gas pipe.
Sensor in the horizontal part of the flue gas pipe:
QGO 20: vertically from above or at an angle of 45°.
QGO 21: horizontal
Sensor in the vertical part of the flue gas pipe:
With a downward inclination of approx. 5°.
45°
45°
5°
QGO 21
QGO 20
min 1 x Ø
Ø
Installation
Weld flange gastight to flue gas pipe
1
, with QGO 20 observe the position of
the flue gas outlet openings
4
.
Install O
2
sensor
2
, ensuring correct alignment of the seal
3
.
Cable entry must be made on the opposite side to the flue gas flow.
1
≥ 1
0 mm
2
3
2
3
1
QGO 20
QGO 21
4