Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
137-228
6.12.15 Adaption
Param & Display
LoadController
Adaption
StartAdaption
AdaptionLoad
Start adaption
The load controller starts automatic adaption via parameter
StartAdaption
.
During adaption, the load controller identifies the controlled system and generates
the PID parameters from the data determined.
Adaption is only possible in modulating operation. It is possible to start in manual or
automatic operation, independent of operating status (burner ON, OFF or
Standby).
During adaption, the filter time
SW_FilterTmeCon
of fault signal suppression
must be 2 … 4 seconds [ch. 6.12.10].
Automatic adaption passes through 4 phases.
Phase
Function
Temp setback
Reduces actual value to 5 % below setpoint.
Stabilisation
phase
The course of the actual value is evaluated for 5 minutes.
If severe fluctuations occur, the time increases to
10 minutes.
Heating
The course of the actual value during heat-up phase is
determined.
Adaption ok
Adaption completed successfully, the PID parameters are
calculated.
Adaption capacity
Parameter
AdaptionLoad
stipulates the burner capacity for automatic adaption.
The adaption capacity should be chosen as large as possible. If the adaption in full
load (100 %) is interrupted due to insufficient heat demand, the adaption capacity
can be reduced by up to 40 %.
If the adaption capacity selected is insufficient, the setpoint temperature will not be
reached and the adaption will be aborted.