6 Operation
83054802 1/2018-07 La
127-228
Output values
Defines the internal value (%, °C, bar or degree of angle) at which 20 mA flow at
output X63.
Setting
Function
Scale20mA prec
Internal percentage value (0 ... 999.9 %) at 20 mA, valid
for:
Load 0
O2
Speed VSD
Flame
Scale20mA temp
Temperature at input X60/X61 (0 ... 2000 °C) at 20 mA,
valid for:
Temp Pt1000
/
Temp Ni1000
/
Temp Pt100
Temp X61
Press X61
Pressure sensor at input X61 (0 ... 99.9 bar) at 20 mA,
valid for
Press X61
.
Scale20mA angle
Actuator position in degree of angle (0 ... 90°) at 20 mA,
valid for:
Pos Air
Pos fuel
Pos Aux…
Scaling (
Scale 0/4mA
)
Parameter
Scale 0/4mA
defines the internal value for the lower current limit.
Depending on parameter
CurrMode 0/4mA
4 mA or 0 mA flow at the value set.
The relative value in percent refers to the output value set (
Scale20mA …
/
Press X61
).