Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
9 Troubleshooting
83054802 1/2018-07 La
201-228
Fault
codes
Diagnostic
code
Cause
Rectification
15
03 … 7F
Actuator position or speed not achieved
If several faults occur, the diagnosis codes
are add up.
01
Position error air actuator
Check mechanics after the actuator for
freedom of movement.
Internal fault
(1
02
Position error fuel actuator
04
Position error auxiliary actuator1
08
Position error auxiliary actuator2
20
Position error auxiliary actuator3
10
Speed not achieved
Check ramp time [ch. 6.9.1].
Check signal line between W-FM and fre-
quency converter.
Check signal line of speed measurement
[ch. 3.3.21].
Check speed standardisation [ch. 6.14.3].
40
Speed difference between setpoint and ac-
tual has exceeded tolerance
16
00
Fault compound curve air actuator
Check compound curve of relevant actu-
ator, if necessary adjust [ch. 6.9.5].
01
Fault compound curve fuel actuator
02
Fault compound curve auxiliary actuator1
03
Fault compound curve auxiliary actuator2
04
Fault compound curve auxiliary actuator3
05
Fault compound curve frequency converter
0A
P- part outside of permissible range
Check O
2
control parameters, if necessary
0B
I- part outside of permissible range
0C
Tau outside of permissible range
0D
O
2
setpoint outside of permissible range
Check values, if necessary readjust O
2
0E
O
2
min value outside of permissible range
0F
O
2
compound value outside of permissible
range
13
Presetting of ABE outside of permissible
range
Internal fault
(1
14
Standardisation value outside of permissible
range
Check values, if necessary readjust O
2
20
Exceeding permissible setpoint position
range
Internal fault
(1
21
Presetting of ABE outside of permissible
range
22
None of the def. cases were met during
switch instruction
23
No defined ELR phase detected during
switch instruction
40
Implausible setpoint position
17
01
Timeout during program run synchronisation
prior to data transfer
Internal fault
(1
02
Timeout during data transfer
03
CRC error during data transfer
3F
Difference detected during data comparison.
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.
Summary of Contents for W-FM 100