Fault
codes
Diagnostic
code
Cause
Rectification
57
00 … 05
Prohibited setting "and not" (
&/
)
The diagnostic code indicates the appropriate
parameter.
00
In
SensExtranlGas
Change setting (OEM level).
01
In
SensExtranlOil
02
In
SensPilotPhGas
03
In
SensPilotPhOil
04
In
SensOperPhGas
05
In
SensOperPhOil
57
06
FGR mode
temp.contr.
is not permitted Function is only available for type LMV52.4…
07
Prohibited setting
HTempGuard
Change setting (OEM level).
08
Prohibited setting
ext.FlameGd
09
FGR mode deviating from
Aux3onCurve
is not permitted
Set
Aux3onCurve
.
0A
Prohibited setting in
AuxActuator
, VSD
and Aux3 not permitted
Change setting (OEM level).
0B
Config X5-03
CoolFctStby
is not permit-
ted
0C
Double assignment input X5-03
Change
LC_OptgMode
or
Config
X5-03
0D
Prohibited setting
HT/FG-RedCo
Change setting (OEM level).
0E
Prohibited setting in
COx
,
OptgMode
COx Gas
and
OptgMode COx Oil
are
deactivated unequally
Function is only available for type LMV52.4…
58
–
Parameter set is corrupted
Reset W-FM, see [ch. 9.1].
If the error occurred during a parameter
change:
Check parameter that was last changed for
plausibility.
If the reset does not achieve a fault free con-
dition:
Load data from the ABE [ch. 6.16.1].
59
–
Parameter set is corrupted
5A
–
Parameter set is corrupted
5B
–
Parameter set is corrupted
5C
–
Data from the ABE was transferred to the
W-FM
Reset W-FM, see [ch. 9.1].
5D
–
Internal fault W-FM
Reset W-FM, see [ch. 9.1].
If the error occurred during a parameter
change:
Check parameter that was last changed for
plausibility.
If the reset does not achieve a fault free con-
dition:
Load data from the ABE [ch. 6.16.1].
5E
–
Internal fault W-FM
5F
–
Data backup was interrupted
Repeat data backup [ch. 6.16.1].
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.
Summary of Contents for W-FM 100