6.12.3 Sensor selection (actual value)
Param & Display
LoadController
Configuration
Sensor select
or
Param & Display
SystemConfig
TempLimiter
Sensor select
To determine the actual value for the internal load controller a sensor has to be
connected to input X60 or X61 [ch. 3.3.20].
The sensor connected is defined in parameter
Sensor select
.
Setting
Function
Pt100
(1
Pt100 sensor at terminal X60:1/2/4
Pt1000
(1
Pt1000 sensor at terminal X60:3/4
Ni1000
(1
Ni1000 sensor at terminal X60:3/4
Pt100Pt1000
(1
Pt100 sensor at terminals X60:1/2/4 for temperature reg-
ulator function.
Pt1000 sensor at terminals X60:3/4 for temperature mon-
itor function.
Pt100Ni1000
(1
Pt100 sensor at terminals X60:1/2/4 for temperature reg-
ulator function.
Ni1000 sensor at terminals X60:3/4 for temperature mon-
itor function.
TempSensor
(2
Temperature sensor at input X61
PressSensor
(2
Pressure sensor at input X61
NoSensor
(2
No sensor connected to W-FM, e. g. external load setting
without temperature monitor function.
(1
The internal temperature monitor function is activated.
(2
The internal temperature monitor function is deactivated.