Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
7 Commissioning
83054802 1/2018-07 La
176-228
7.3 Load controller
The W-FM 200 is equipped with an internal PID load controller as standard, with
the W-FM 100 the internal load controller is optional.
Commissioning must only be carried out by qualified personnel.
7.3.1 Configure load controller
1. Enter password
Select
Param & Display
.
Select
Access with HE
(password for heating engineer).
Enter HE password using dial knob and confirm with [ENTER] [ch. 6.2.1].
2. Set operating mode
Select
LoadController
.
Select
Configuration
.
Select
LC_OptgMode
.
Set operating mode for the internal or external load controller using dial knob
and confirm with [Enter] [ch. 6.12.2].
Use [esc] key to return to the display
LC_OptgMode
.
3. Define sensors
For operating mode with internal load controller and temperature monitor function,
the connected sensors must be defined [ch. 3.3.20].
Select
Sensor Select
.
Define connected sensor with the dial knob and confirm with [Enter [ch. 6.12.3].
Use [esc] to return to the display
Sensor Select
.
To ensure the actual value is entered correctly, the measuring range of the sensors
must be defined [ch. 6.12.5].
Select menu for the sensor defined and confirm with [Enter].
Sensor:
MeasureRangePtNi
/
var.RangePtNi
Temperature sensor:
MRange TempSens
Pressure sensor:
MRange PressSens
Set end of measuring range using dial knob and confirm with [Enter].
Use [esc] to return to the menu.
If a sensor is connected, input X61 has to be matched to the sensor [ch. 6.12.4].
Select
Ext Inp X61 U/I
.
Set analogue signal from the sensor.
Use [esc] to return to the display
Ext Inp X61 U/I
.
4. Configuring analogue input X62
If an analogue setpoint or load signal is present at input X62, the input must be
matched to the signal [ch. 6.12.4].
Select
Ext Inp X62 U/I
.
Match input to the analogue signal.
Use [esc] to return to the display
Ext Inp X62 U/I
.