Configuration

Sensor is supplied with a basic programming which is the one 

indicated as default in the chapter of the technical features.
To change these settings, disconnect the device, make all the 

necessary settings using the triple jumpers J4 or the Dip Switch 

SW1 shown in the figure and supply the device again; in partic-

ular

4…20mA Output reference selection:

Sensor is basic set to have the negative of the supply signal 

as the 4÷20mA signal reference; to change this setting it is 

necessary to move the triple jumpers J4 as shown in the 

figure:

                    Ref. to - (default)         Ref. to +

4…20mA Output Signal Type Configuration

To set the 4…20mA output signal type, operator has to use 

the 5th selector of the dip-switch in SW1 position, particu-

larly:

Alarm Thresholds Settings: 

To set the intervention thresholds of the optional relay board 

or of the 4÷20mA output threshold operation, it is neces-

sary to act on the first four dip-switch selectors of the SW1 

position; in particular thresholds expressed as a percentage 

of the Full Scale are the followig:

(*) When the first four dip-switch selectors are in the OFF position, 

the trip thresholds can be only set by TUS40.. service and mainte-

nance terminal or via  Display (DR ... or DN Board ...). In the event 

that this selection is made without the presence of the service 

terminal, the device will take the default thresholds as intervention 

thresholds. For the use of the terminal see the relative operating 

manual. If the Display Board DR- or DN- is present, TUS40.. termi-

nal is not usable.

Mechanical Installation of the 

optional Relay Card or optional 

PhotoMos Cards with resistive 

output variation

On the main electronic card it is possible to insert, in a special 

connector named CN1, a module having on board N. 4 relays 

with changeover contact that will be activated in correspon-

dence of the pre-alarm events, 1st alarm threshold, 2nd alarm 

threshold and faulty sensor, and the relative LEDs signaling.

Follow the steps below to insert the card:

Electrical Installation of the 

optional Relay Card 

After the relay card is mechanically installed it is necessary to 

provide for its electrical configuration by selecting the relay 

control logic and the type of contact that is required on the 

terminal board (NC or NO).

Elastic Flag

Proportional Output 

(4…20mA)

Step Output (0-10-20mA)

CN1 Connector

Phase 1

Insert on the main 

electronic card the 

card guide supplied 

with the card, taking 

care to turn the elastic 

flag towards the main 

terminal board. 

Locate the 

connector CN1.

Card Guide

(with Elastic Flag)

Phase 2

Fully insert the card, taking care to pull 

the elastic flag of card guide towards the 

terminal board of the optional card.

Phase 3

Check the positioning of the card checking that 

all pins are internal to the CN1 connector and 

that, by practing a slight pull upwards, the card 

remains in position due to correctly hooked 

and held by the elastic flag of the card guide.

Phase 4

Mark the box showing the presence 

of the relay card inside the device 

with a permanent marker.

2
1

2
1

6
5

6
5

Summary of Contents for UR.21.S

Page 1: ...WattsWater eu UR 21 S ATEX II 3G Ex nA nC d IIC T6 1 Gb certified Installation manual Installation and Operation Manual Manuale di Installazione e Uso Manual de instalaci n y funcionamiento UK IT ES...

Page 2: ...with 4 20mA with s c output 2 4W 4W with UZR20 4 1 2W 2 8W with UZR20 4 Measuring range 0 100 LEL 3 0 500 ppm Precision Catalytic E C NDIR 5 of Full Scale 10 readout Precision Semiconductor 10 of Full...

Page 3: ...of each Relay and separate quick connecting term blocks Relay A Pre alar 10 LEL 50 ppm Relay B 1st Thresh Alarm 20 LEL 100 ppm Relay C 2nd Thresh Alarm 40 LEL 200 ppm Relay D Detector Fail The state...

Page 4: ...ility and disposal This product has been designed and constructed using materials and processes that take into account the environ mental issue Refer to the following notes for disposal of the product...

Page 5: ...ds For the use of the terminal see the relative operating manual If the Display Board DR or DN is present TUS40 termi nal is not usable Mechanical Installation of the optional Relay Card or optional P...

Page 6: ...lay board are energized or de energized if SW1 6 is set to ON Troubleshooting For troubleshooting having only one LED that identifies the func tional states described in the table above when operating...

Page 7: ...for use in Zone 2 G Equipment intended for use in explosive gas atmosphere caused by mixture of air and gas vapours flammable mists Ex nA nC d IIC T6 1 Gb Type of protection according to EN60079 0 EN6...

Page 8: ...mpo di misura 0 100 LIE 3 0 500 ppm Precisione Catalitico C E NDIR 5 del Fondo Scala 10 della lettura Precision Semiconductor 10 odel Fondo Scala sul punto di taratura Repeatability 5 del Fondo Scala...

Page 9: ...cheda Display DR o DN Disponibili contatti NA o NC selezionabili a mezzo ponticelli Valori di default per infiammabili e CO La scheda dotata di n 4 led associati allo stato di ciascun Rel e morsettier...

Page 10: ...tardi possibile per evitarne danneggiamenti ma comunque in tempo utile per proteggere adeguatamente l ambiente a cui sono desti nati Compatibilit ambientale e smaltimento Questo prodotto stato svilupp...

Page 11: ...ositivo assum er come soglie di intervento quelle di default Per l utilizzo del terminale vedere il relativo manuale operativo In caso di presenza della Scheda Display DR o DN il Terminale TUS40 non p...

Page 12: ...ato su ON Ricerca Guasti Per la ricerca guasti disponendo di un solo led che identificati gli stati funzionali descritti nella tabella qui sopra in caso di guasto od anomalia funzionale oltre ai consu...

Page 13: ...Zona 2 G Apparecchio utilizzabile in atmosfera potenzialmente esplosive per la presenza di gas vapori nebbie infiammabili Ex nA nC d IIC T6 1 Gb Tipo di protezione in accordo a EN60079 0 EN60079 15 e...

Page 14: ...00 LIE 3 0 500 ppm Precisi n Catal tico C E NDIR 5 del fondo escala 10 de la lectura Precisi n Semiconductor 10 del fondo escala en el punto de calibraci n Repetibilidad 5 del fondo escala 10 de la le...

Page 15: ...puentes Valores predeterminados para inflamable y CO La placa est equipada con 4 LED asociados con el estado de cada rel y bloques de terminales de acoplamiento r pido separados Rel A Pre alarma 10 L...

Page 16: ...tiempo para proteger adecuadamente el medio ambiente al que est n destinados Respeto al medio ambiente y eliminaci n Este producto ha sido desarrollado y construido utili zando materiales y procesos...

Page 17: ...itivo tomar los umbrales predetermi nados como umbrales de intervenci n Para el uso del terminal Instalaci n mec nica de la Tarjeta Opcional de Rel s o de las Tarjetas Opcionales PhotoMos con variaci...

Page 18: ...0 del LEL del gas Metano o a 500ppm para el CO utilizando el kit de prueba tiempo de aplicaci n del gas de prueba 2 minutos aseg rese de que la salida 4 20mA est entre los 11 y 13 mA para metano o ent...

Page 19: ...ble en atmosfera potencialmente explosiva debido a la presencia de gas vapores nieblas inflamables Ex nA nC d IIC T6 1 Gb Tipo di protecci n de acuerdo a a EN60079 0 EN60079 15 e EN60079 29 1 cuerpo d...

Page 20: ...consentimiento del comprador a los t rminos y condiciones de Watts que se encuentran en su sitio web en www wattswater eu Watts se opone a cualquier t rmino diferente o adicional a los t rminos de Wa...

Reviews: