UR21S-MOI-IT-W-ML-10-22-Rev0

Watts Water Technologies, Inc.

EN

General

Power supply 10 Power supply 10÷28Vdc. Sensitive elements:

• 

Catalytic (S and P), Infrared (I) or Semiconductor (T) for flammable gases,

• 

Electrochemical cell (S or P), Infrared (I) or Semiconductor (T) for toxic and refrigerant gases.

Up to three intervention thresholds. Automatic counting of the lifetime of the sensors. 

LED on the sensor body to indicate the operating status and display option.

Use

UR21S detectors are used to detect, by diffusion, the presence of:

Methane Gas, code 0940571N; LPG, code 0940572N; Carbon Monoxide (CO), code 0940573N. Other gases are on request.

The UR21S detectors are designed for Stand-Alone operation with a 4÷20mA output and for interfacing with the CIVIC1 and 

CIVIC4 Central Units.

 

Operation

In case of a gas leak the sensor compares the measured concentration value with the intervention thresholds set by activating the 

relays or the resistive outputs (if provided) associated with them. The information of the measured concentration value is always 

present on the 4 ÷ 20mA output

Technical Characteristics

Sensor type

Catalytic, Infrared, or 

Semiconductor

Electrochemical Cell or 

Semiconductor

Detectable Gas

Explosive Gases

(2)

Toxic Gases (e.g.: CO)

Power supply

10÷28Vdc

10÷28Vdc

Maximum Power Consumption (@ 28Vdc with 

4÷20mA with s.c. output)

2,4W

(4W with UZR20.4)

1.2W

(2,8W with UZR20.4)

Measuring range 

0÷100% LEL

(3)

0÷500 ppm 

Precision (Catalytic, E.C., NDIR)

±5% of Full Scale.                                 ±10% readout

Precision (Semiconductor)

±10% of Full Scale                                (on calibration point)

Repeatability

±5% of Full Scale.                                 ±10% readout

Measurement Resolution (Sensivity)

1% LEL

5 ppm

Microprocessor Resolution

4096 points (12 bit A/D Converter)

Digital Filter system

Kalman Filter and zero drift compensation

Watch dog

External, acting on the whole Safety Chain

Warm-up Time

< 2 minutes after every power on

Stabilization Time

2 hours from first power on

Response Time (Max)

< 20s (T50), < 60s (T90)

Average Sensor Life (in Air)

255 weeks

255 weeks

Output 4÷20mA signal type:

Proportional Output

(default)

Step Output

(1 o 2 thresholds application)

Settable reference of 4÷20mA signal 

-   4mA   =     0% LEL;         0 ppm

- 20mA   = 100% LEL;     500 ppm

-   0mA   = no Alarm

- 10mA   = 1st  Threshold Alarm

- 20mA   = 2nd  Threshold Alarm

With jumpers (reference to negative or positive of power supply)

Load Resistance of 4…20mA output (with 

generator limited to 24mA)

Minimum  

0Ω @ 28Vdc

Maximum  

300Ω @ 10Vdc

Operation and storage conditions:

Environment Temperature (°C)

- Operating

- Storage

-20 ÷ 50   or   -40 ÷ 70  (Extended Range)

-20 ÷ 70

Relative Umidity (%UR) without condens.         

 -    Operating

- Storage

15 ÷ 90

45 ÷ 75

Operating Pressure (KPa)

80 ÷ 120

Air Speed (m/s)

 6

Optical Signalling

Red LED visible on the sensor body

Dimensions and Weight

See dedicated paragraph

ATEX Marking

           II 3G Ex nA nC d IIC T6(1) Gb

-20°C ≤ TA ≤ +50°C

-40°C ≤ TA ≤ +70°C (Extended Range)

Manufacturer EsiWelma

Summary of Contents for UR.21.S

Page 1: ...WattsWater eu UR 21 S ATEX II 3G Ex nA nC d IIC T6 1 Gb certified Installation manual Installation and Operation Manual Manuale di Installazione e Uso Manual de instalaci n y funcionamiento UK IT ES...

Page 2: ...with 4 20mA with s c output 2 4W 4W with UZR20 4 1 2W 2 8W with UZR20 4 Measuring range 0 100 LEL 3 0 500 ppm Precision Catalytic E C NDIR 5 of Full Scale 10 readout Precision Semiconductor 10 of Full...

Page 3: ...of each Relay and separate quick connecting term blocks Relay A Pre alar 10 LEL 50 ppm Relay B 1st Thresh Alarm 20 LEL 100 ppm Relay C 2nd Thresh Alarm 40 LEL 200 ppm Relay D Detector Fail The state...

Page 4: ...ility and disposal This product has been designed and constructed using materials and processes that take into account the environ mental issue Refer to the following notes for disposal of the product...

Page 5: ...ds For the use of the terminal see the relative operating manual If the Display Board DR or DN is present TUS40 termi nal is not usable Mechanical Installation of the optional Relay Card or optional P...

Page 6: ...lay board are energized or de energized if SW1 6 is set to ON Troubleshooting For troubleshooting having only one LED that identifies the func tional states described in the table above when operating...

Page 7: ...for use in Zone 2 G Equipment intended for use in explosive gas atmosphere caused by mixture of air and gas vapours flammable mists Ex nA nC d IIC T6 1 Gb Type of protection according to EN60079 0 EN6...

Page 8: ...mpo di misura 0 100 LIE 3 0 500 ppm Precisione Catalitico C E NDIR 5 del Fondo Scala 10 della lettura Precision Semiconductor 10 odel Fondo Scala sul punto di taratura Repeatability 5 del Fondo Scala...

Page 9: ...cheda Display DR o DN Disponibili contatti NA o NC selezionabili a mezzo ponticelli Valori di default per infiammabili e CO La scheda dotata di n 4 led associati allo stato di ciascun Rel e morsettier...

Page 10: ...tardi possibile per evitarne danneggiamenti ma comunque in tempo utile per proteggere adeguatamente l ambiente a cui sono desti nati Compatibilit ambientale e smaltimento Questo prodotto stato svilupp...

Page 11: ...ositivo assum er come soglie di intervento quelle di default Per l utilizzo del terminale vedere il relativo manuale operativo In caso di presenza della Scheda Display DR o DN il Terminale TUS40 non p...

Page 12: ...ato su ON Ricerca Guasti Per la ricerca guasti disponendo di un solo led che identificati gli stati funzionali descritti nella tabella qui sopra in caso di guasto od anomalia funzionale oltre ai consu...

Page 13: ...Zona 2 G Apparecchio utilizzabile in atmosfera potenzialmente esplosive per la presenza di gas vapori nebbie infiammabili Ex nA nC d IIC T6 1 Gb Tipo di protezione in accordo a EN60079 0 EN60079 15 e...

Page 14: ...00 LIE 3 0 500 ppm Precisi n Catal tico C E NDIR 5 del fondo escala 10 de la lectura Precisi n Semiconductor 10 del fondo escala en el punto de calibraci n Repetibilidad 5 del fondo escala 10 de la le...

Page 15: ...puentes Valores predeterminados para inflamable y CO La placa est equipada con 4 LED asociados con el estado de cada rel y bloques de terminales de acoplamiento r pido separados Rel A Pre alarma 10 L...

Page 16: ...tiempo para proteger adecuadamente el medio ambiente al que est n destinados Respeto al medio ambiente y eliminaci n Este producto ha sido desarrollado y construido utili zando materiales y procesos...

Page 17: ...itivo tomar los umbrales predetermi nados como umbrales de intervenci n Para el uso del terminal Instalaci n mec nica de la Tarjeta Opcional de Rel s o de las Tarjetas Opcionales PhotoMos con variaci...

Page 18: ...0 del LEL del gas Metano o a 500ppm para el CO utilizando el kit de prueba tiempo de aplicaci n del gas de prueba 2 minutos aseg rese de que la salida 4 20mA est entre los 11 y 13 mA para metano o ent...

Page 19: ...ble en atmosfera potencialmente explosiva debido a la presencia de gas vapores nieblas inflamables Ex nA nC d IIC T6 1 Gb Tipo di protecci n de acuerdo a a EN60079 0 EN60079 15 e EN60079 29 1 cuerpo d...

Page 20: ...consentimiento del comprador a los t rminos y condiciones de Watts que se encuentran en su sitio web en www wattswater eu Watts se opone a cualquier t rmino diferente o adicional a los t rminos de Wa...

Reviews: