WL2 FW
Manual
Page 55 – Revision EU05-07-17
2.
Red Heater & Compressor Power Switch is lit but the Red LED on the Front is not
lit
Possible Reason
Solution
Bad Transformer
Replace Transformer
Black Power Connector to the
PCB is not properly connected
Properly connect.
Bad Front PCB
Replace Front PCB
Defective Red Heater &
Compressor Switch
Replace Red Heater & Compressor Switch
3.
Compressor Runs But Does Not Chill
Possible Reason
Solution
Condenser is dirty
Clean the condensing coil of any obstructions or dust.
Reduction of airflow into unit.
Make sure unit is not under minimum ventilation requirements (2
to 4 inches).
Compressor is running very
hot.
Low or lost refrigerant.
Mini should be 20 grams
Free standing should be 22 grams
Refrigerant recharge as necessary.