WAGO-I/O-SYSTEM 750 XTR
Modbus – CODESYS 2 307
750-8212/040-010 PFC200 G2 2ETH M12 RS XTR
Manual
Version 1.0.0, valid from FW version 03.01.07(13)
10.3.2 Modbus TCP Settings
The “Modbus TCP Settings” contains the following configuration parameters for
the “Modbus TCP” mode:
Table 214: Modbus TCP Settings
Parameters Explanation
TCP mode
Enable for the Modbus TCP mode
Off
Operation not permitted
Active
*
Operation possible
TCP port
Port number for the TCP link
1
Minimum port number
502
*
Modbus default port
65535
Maximum port number
TCP Timeout Time-out for a TCP link
1
100 ms (1 × 100 ms)
600
*
60 seconds (600 × 100ms)
65535
1 h 49 min 13 s 500 ms (65535 × 100 ms)
*
Default setting
10.3.3 Modbus UDP Settings
The “Modbus UDP Settings” group contains the following configuration
parameters for the “Modbus UDP” mode:
Table 215: Modbus UDP Settings
Parameters Explanation
UDP mode
Enable for the Modbus UDP mode
Off
Operation not permitted
Active
*
Operation possible
UDP port
Port number for the UDP link
1
Minimum port number
502
*
Modbus default port
65535
Maximum port number
*
Default setting
10.3.4 Modbus RTU Settings