WAGO-I/O-SYSTEM 750 XTR
Run-time System CODESYS 2.3 253
750-8212/040-010 PFC200 G2 2ETH M12 RS XTR
Manual
Version 1.0.0, valid from FW version 03.01.07(13)
3.
Right-click on the entry “K-
Bus[FIX]
” and then select “Edit” in the contextual
menu. The “configuration” dialog window then opens.
Figure 60: Control Configuration – Edit
4.
There are three options for accepting the topology for the I/O modules
connected to the fieldbus controller. The simplest way is to scan in the
topology using WAGO-I/O-
CHECK
.
To do this, click on the “Start WAGO-I/O-
CHECK
and scan” button.
Figure 61: “Start WAGO-I/O-
CHECK
and Scan” Button
Ensure proper installation of WAGO-I/O-
CHECK
!
This function requires that the latest version of WAGO-I/O-
CHECK
be installed
and the IP address set under “Online > Communication parameters”, as
otherwise communication will not be possible.