368 Appendix
WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
long: dimming, darker
Bit pairs GA1 … GA15 similar to
GA0.
11
Bit 8…15
Bit 0…7
Switch scene 0…15
DA = DALI address
GA = Group address
15.1.5.13 LON
®
FTT Module
753-648
The process image of the LON
®
FTT module consists of a control/status byte and
23 bytes of bidirectional communication data that is processed by the WAGO-I/O-
PRO
function block "LON_01.lib". This function block is essential for the function
of the LON
®
FTT module and provides a user interface on the control side.
15.1.5.14 EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 2
words mapped into each image. Word alignment is applied.
Table 285: EnOcean Radio Receiver 750-642
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
D0
S
Data byte
Status byte
1
D2
D1
Data bytes
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
C
not used
Control byte
1
-
-
not used
15.1.5.15 MP Bus Master Module
750-643
The MP Bus Master Module has a total of 8 bytes of user data in both the Input
and Output Process Image (6 bytes of module data and 2 bytes of control/status).
The following table illustrates the Input and Output Process Image, which have 4
words mapped into each image. Word alignment is applied.