WAGO-I/O-SYSTEM 750
MODBUS – e!RUNTIME 307
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
11.2 MODBUS Registers
Table 216: WAGO MODBUS Registers
MODBUS Address Data Length
in Words Access Description
Dec.
Hex.
Watchdog Configuration Registers
64,000
0xFA00
1
w
Watchdog command register
64,001
0xFA01
1
rw
Watchdog timeout register
64,002
0xFA02
1
ro
Watchdog status register
64,003
0xFA03
1
rw
Watchdog config register
64,004
0xFA04
1
rw
MODBUS TCP connection
watchdog register
Status Registers
64,010
0xFA0A
1
ro
LED flash code I/O-LED
(sequence 1 of 3)
64,011
0xFA0B
1
ro
LED flash code I/O-LED
(sequence 2 of 3)
64,012
0xFA0C
1
ro
LED flash code I/O-LED
(sequence 3 of 3)
64,013
0xFA0D
1
ro
PLC State : 1 = Stop; 2 = Run
Electronic Type Label
64,016
0xFA10
4
ro
Order number, e.g.,
0750810100400001
64,020
0xFA14
1
ro
Firmware status
64,021
0xFA15
1
ro
Hardware version
64,022
0xFA16
1
ro
Firmware loader
Process Image Version
64,023
0xFA17
1
ro
Version of the MODBUS process
image
Network Configuration
64,032
0xFA20
3
ro
MAC-ID 1
Process Image Registers
64,064
0xFA40
1
ro
Number of input registers, analog
and digital (total size of the
MODBUS IN space) 0x7D00
64,065
0xFA41
1
ro
Number of input registers, analog
0x7D00
64,066
0xFA42
1
ro
Number of input registers, digital
0x8000
64,067
0xFA43
1
ro
Number of output registers,
analog and digital (total size of
the MODBUS OUT space)
0x7D00
64,068
0xFA44
1
ro
Number of output registers,
analog 0x7D00