WAGO-I/O-SYSTEM 750
Appendix 357
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
15.1.5 Specialty Modules
WAGO has a host of Specialty I/O modules that perform various functions. With
individual modules beside the data bytes also the control/status byte is mapped
in the process image.
The control/status byte is required for the bidirectional data exchange of the
module with the higher-ranking control system. The control byte is transmitted
from the control system to the module and the status byte from the module to the
control system.
This allows, for example, setting of a counter with the control byte or displaying of
overshooting or undershooting of the range with the status byte.
The control/status byte always is in the process image in the Low byte.
Information to the structure of the Control/Status byte
For detailed information about the structure of a particular module’s control/status
byte, please refer to that module’s manual. Manuals for each module can be
15.1.5.1 Counter Modules
750-404, (and all variations except of /000-005),
753-404, (and variation /000-003)
The above Counter Modules have a total of 5 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 1 byte of control/status).
The counter value is supplied as 32 bits. The following tables illustrate the Input
and Output Process Image, which has a total of 3 words mapped into each
image. Word alignment is applied.
Table 267: Counter Modules 750-404, (and all variations except of /000-005),
753-404, (and variation /000-003)
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
S
Status byte
1
D1
D0
Counter value
2
D3
D2
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
C
Control byte
1
D1
D0
Counter setting value
2
D3
D2