WAGO-I/O-SYSTEM 750
Commissioning 115
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
7.8.1.9 “Ethernet Configuration” Page
The settings for Ethernet TCP/IP are located on the “Ethernet Configuration”
page.
7.8.1.9.1 “Switch Configuration” Group
Table 53: WBM “Ethernet Configuration” Page – “Switch Configuration” Group
Parameter
Explanation
Interfaces
Enable or disable the switch.
Switched
Both interfaces are operated with one
IP address.
Separated Each interface is operated with its own
IP address.
Port Mirror
Enable or disable the mirroring of the data traffic
between the ports.
None
Both Ethernet ports operating normally.
X1
The entire data traffic between X1 and
the PFC system is mirrored at port X2.
X2
The entire data traffic between X2 and
the PFC system is mirrored at port X1.
Fast Aging enabled
Set here the aging time of unused entries in the list
of MAC addresses with a port assignment to
external network stations.
Disabled
An unused address entry becomes
obsolete after 200 seconds.
Enabled
An unused address entry becomes
obsolete after 800 microseconds.
Broadcast Protection
Set here the broadcast limit for protection against
overloads.
Disabled
No limitation of broadcast packets.
1 % ... 5 %
Limitation of incoming broadcast
packets to the selected percentage of
the total possible data throughput
(10/100Mbit).
Rate Limit
Set here the basic limitation of the incoming data
traffic.
Disabled
No limitation of the incoming data traffic
64 kbps …
99 mbps
Limitation of the incoming data traffic to
the entered value
Click
[Submit]
to apply the change. The change is effective immediately.
7.8.1.9.2 “Interface Xn” Groups
One group (“Interface X1” / “Interface X2”) is displayed for each connection.