Table 306: Description of Configuration Scripts for “Ports and Services” – “Network Services
Parameters Status Call-Up
Output/Input
Valid
Network Services
Telnet
Telnet Port
read
get_port_state
telnet
Read the status of the Telnet
server.
Possible return values:
- enabled
- disabled
Right
away
write
config_port
port=telnet
state=<Value>
Possible entries for <Value>:
- enabled
- disabled
FTP
FTP Port
read
config_ssl
ftp-status
Read the status of the FTP
server.
Possible return values:
- enabled
- disabled
Right
away
write
config_port
port=ftp state=<Value>
Possible entries for <Value>:
- enabled
- disabled
FTPS
FTPS Port
read
config_ssl ftps-status
Read the status of the FTPS port.
Possible return values:
- enabled
- disabled
Right
away
write
config_port port=ftps
state=<Value>
Activate/Deactivate FTPS.
Possible entries for <Value>:
- enabled
- disabled
HTTP
HTTP Port
read
config_ssl http-status
Read the status of the HTTP port.
Possible return values:
- enabled
- disabled
Right
away
write
config_port port=http
state=<Value>
Activate/Deactivate HTTP.
Possible entries for <Value>:
- enabled
- disabled
HTTPS
HTTPS Port
read
config_ssl https-status
Read the status of the HTTPS
port.
Possible return values:
- enabled
- disabled
Right
away
write
config_port port=https
state=<Value>
Activate/Deactivate HTTPS.
Possible entries for <Value>:
- enabled
- disabled