384 Appendix
WAGO-I/O-SYSTEM 750
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
Table 302: Description of the Configuration Scripts for “NTP”
Parameters Status Call
Output/Input
Effecti
ve
Configuration Data
State
read
get_ntp_config
state
Query the status of the NTP
server
Possible return values are:
- enabled
- disabled
Immedia
tely
write
config_sntp
state=<Value>
Possible entries for <Value>:
- enabled
- disabled
Port
read
get_ntp_config
port
Port number of the NTP server
Immedia
tely
write
config_sntp
port=<Value>
Enter the port number for
<Value>.
Time Server
read
get_ntp_config
time-server-<N>
Query the IP address of the time
server: N = 1 … 4 for querying
one of 4 time servers.
Immedia
tely
write
config_sntp
time-server-
<N>=<Value>
Enter the IP address of 4 time
servers
<N> can be a value from 1 to 4.
<Value> is an IP address with the
format “Number. Number.
Number. Number.”
Update Time
(seconds)
read
get_ntp_config
update-time
Query the time in seconds
between two requests to the time
server.
Immedia
tely
write
config_sntp
update-time=<Value>
Specify the time-server's query
cycle (in s) for <Value>.