61: interlock2
62: interlock3
63: PFC start/stop
64: A frequency switch B and run
65~99: reserved
F7.07
Reserved
—
—
0
◆
F7.08
Digital filtering
times
1~10 1: 2MS unit of scanning time
1
5
o
F7.09
Terminal function
detection when
power on
0: terminal operation command invalid
when power on
1: terminal operation command valid
when power on
1
0
o
F7.10
Effective logic
setting of input
terminal (X1~X7)
0~7FH
0 is positive logic, i.e. terminal Xi is
enabled when it connects with common
terminal and disabled if disconnected.
1 is negative logic, i.e. terminal Xi is
disabled when it connects with common
terminal and enabled when disconnected.
1
00
×
F7.11
FWD/REV terminal
control mode
0: two-wire control mode 1
1: two-wire control mode 2
2: three-wire control mode 1
3: three-wire control mode 2
1
0
×
F7.12
UP/DOWN
terminal frequency
modifying rate
0.01~50.00Hz/S
0.01Hz/
S
1.00
o
F7.13
reserved
—
—
0
◆
F7.14
Y1 output delay
0.0~100.0s
0.1S
0.0
×