Fig.F9-6 Traverse Operation
Note:
1: the central frequency is the frequency of digital
setting, analog setting, impulse, PLC or MS running.
2: the traverse is invalid for jog or closed loop running.
3: when both PLC and traverse are enabled, the
traverse is invalid when transferring to another PLC
stage. The output frequency begins to traverse after
arriving at the PLC preset frequency within Acc/Dec
time. When receiving stop command, the driver will
stop according to PLC Dec time.
F9.66
reserved
Reserved
0
F9.67
Length control
0~1
0
0: disabled
1: enabled
F9.68
Preset length
0.000~65.535(KM)
0.000
F9.69
Actual length
0.000~65.535(KM)
0.000
F9.70
Length factor
0.100~30.000
1.000
F9.71
Length calibration
0.001~1.000
1.000
F9.72
Shaft circumference
0.10~100.00CM
10.00
F9.73
Pulse per revolution(X6)
1~65535
1000
These above parameters are used for length control.
The counting pulse is input from terminal X6 defined
as function NO.53. The length is calculated based on
F9.73 and F9.72.
Calculated length=number of counting pulse÷number
of pulse per revolution×shaft circumference
After correcting the calculated length by F9.70 and
F9.71, the actual length is obtained.
Actual length=calculated length×F9.70÷F9.71
When the actual length(F9.69)≥preset length(F9.68),
the driver will stop automatically. You must clear the
actual length record(F9.69)record or modify the