160
LED thousand’s palce: reserved
FC.26
Oscillation suppression upper limit freqency
0.00~300.00Hz
50.00
FC.27
Oscillation suppression coefficient
1~500
50
FC.28
Oscillation suppression voltage
0.0~25.0%*motor rated voltage
5.0
FC.27~FC.28 see details for FC.19 instruction.
FE
Panel
Function
Setting
and
Parameter
Management(PD group reserved)
FE.00
LCD language option (LCD)
0~2
0
0: Chinese
1: English
2: reserved
FE.01
Key M-FUNC function
0~4
0
0: JOG(jog control)
M-FUNC
key is for jog control, and the default
direction is set by F0.21.
1: FWD/REV switch
M-FUNC
equals direction switch key in running
status, and is disabled in stop status. This switching is
only effective to command giving method of keypad.
2: clear frequency set by
FE.02
Key STOP/RST function
0~3
3
0: only effective to panel control
Only when F0.06=0, this key can control the driver to
stop.
1: effective to both panel and terminal control
Only when F0.06=0 or 1, can this key control the driver
to stop. In the communication control mode, this key
is invalid.
2: effective to both panel and communication control
Only when F0.06=0 or 2, can this key control the driver
to stop. In terminal control mode, this key is invalid.
3: effective to all control modes
This key can control the driver to stop in all control
modes.
Notice:
In all command giving methods, reset function is
enabled.
FE.03
STOP + RUN emergency stop
0~1
1
0: disabled
1: coast to stop
Press
RUN
and
STOP/RESET
, the driver will
Summary of Contents for VTS5000 Series