![VTS Medical Systems VTS5000 Series Operating Instructions Manual Download Page 140](http://html1.mh-extra.com/html/vts-medical-systems/vts5000-series/vts5000-series_operating-instructions-manual_1056181140.webp)
136
2) if feedback value increases to above reference value,
the sleep mode is entered after delay time
【
F8.17
】
;
otherwise, if the feedback value decreases to under
wake-up threshold
【
F8.16
】
, it will wake up
immediately.
F8.13
Stop method of sleep mode
0~1
0
0: decelerate to stop
1: coast to stop
F8.14
Deviation limit of feedback when entering
sleep state compared with set pressure
0.0~20.0%
0.5%
This function parameter is only valid to the second
sleep mode.
F8.15
Threshold value of sleep
0.00~200.0%
100.0%
This threshold value is the percentage of set pressure
value. This parameter is only valid to the first sleep
mode.
F8.16
Threshold value of wake-up
0.00~200.0%
90.0%
F8.15 defines the feedback value when the driver is
entering sleep mode. If the actual feedback is larger
than this set value, and the output frequency arrives
at lower limit, the driver will enter sleep mode (zero
speed operation) after delay time defined by F8.17.
F8.16 defines the feedback limit when the driver is
entering operating state from sleep mode. When PID
selects positive characteristic and the the actual
feedback is smaller than this set value (or when PID
selects negative characteristic and the actual feedback
is larger than this set value), the driver will start to
operate from sleep mode after delay time defined by
F8.18.
Fig. F8-5 the First Sleep Mode
Summary of Contents for VTS5000 Series