111
F6 analog and impulse parameters of input and output
F6.00
AI1 input corresponding physical quantity
0~2
0
0:
speed
command
(output
frequency,
-100.0%~100.0%)
1: torque command (output torque, -200.0%~200.0%)
AI1 analog setting value works as torque
command
value,
given
torque
range
is
-200.0%~200.0%. Relevant setting see F6 group
function code description.
2:
voltage
command
(output
voltage,
0.0%~200.0%*motor rated voltage)
F6.01
AI1 input lower limit
0.00V/0.00mA~10.00V/20.00mA
0.00
F6.02
AI1 lower limit corresponding physical
quantity setting
-200.0%~200.0%
0.0%
F6.03
AI1 input upper limit
0.00V/0.00mA~10.00V/20.00mA
10.00
F6.04
AI1 upper limit corresponding physical
quantity setting
-200.0%~200.0%
100.0%
F6.05
AI1 input filtering time
0.00s~10.00s
0.05
F6.06
AI2 input corresponding physical quantity
0~2
0
0:
speed
command(output
frequency,
-100.0%~100.0%)
1: torque command(output torque, -200.0%~200.0%)
AI1 analog setting value works as given value of
torque command, which ranges -200.0%~200.0%.
For relevant setting see F6 group function code
description.
2:
voltage
command(output
voltage,
0.0%~200.0%*motor rated voltage)
F6.07
AI2 input lower limit
0.00V~10.00V
0.00
F6.08
AI2 lower limit corresponding physical
quantity setting
-200.0%~200.0%
0.0%
F6.09
AI2 input upper limit
0.00V~10.00V
10.00
F6.10
AI2 upper limit corresponding physical
quantity setting
-200.0%~200.0%
100.0%
F6.11
AI2 input filtering time
0.00s~10.00s
0.05
These above function codes defined input range of
analog input voltage channel AI1, AI2, and the
corresponding physical quantity percentage and
filtering time constant. AI1 can be chosen as
voltage/current input via J1 wire jumper, and the
digital setting can be based on the relation of 0~20mA