Displayed
code
Protection description
Recommended solution
P001
The leakage
current is too high
1.Cut off the DC breaker and check if there is ab-
normity in the AC side;
2.After the fault is removed, close the DC breaker
and restart the inverter;
3.If the fault occurs repeatedly, pleas ask for
professional service.
1.Check if the inverter is normally connected to
the grid;
2.Check if the grid voltage and frequency are
complying with the output scope of the inverter;
3.If the fault above is removed but the inverter can
still not work normally, please ask for professional
service.
1.Cut off the DC breaker;
2.Check if the resistance between the +/- poles of
the PV assembly and the ground is larger than1M ;
3.If the fault above is removed but the inverter can
still not work normally, please ask for professional
service.
Ω
1.Cut off the DC breaker;
2.Check if DC input is higher than 550V;
3.If the fault above is removed but the inverter can
still not work normally, please ask for professional
service.
P002
The voltage at the
grid side is too high
P003
P004
The voltage at the
grid side is too low
P005
P006
Tab. 6-1: Protection code and solution
The frequency at the
grid side is too high
The frequency at the
grid side is too low
Islanding protection
P007
The insulating
impedance is too low
P013
P014
The DC current input
is too high
The DC voltage is
too high
Victory Power New Energy
VP-UMSC1.0.0EN
39
/47
Troubleshooting and maintenance
ShiniCube1600TL-3300TL User Manual