No. Name
lower
upper
default
UOM
Description
limit
limit
settinglimit
limit
setting
26
CH_low_hyst_on
0
20
5
°C
Start hysteresis in low circuit calculated
on the mixer outlet temp
27
CH_low_hyst_off
0
20
3
°C
Stop hysteresis in low circuit calculated
on the mixer outlet temp
28
Mix_valve_step_ open_time 0
255
5
s
For each step the valve opens
1/2 of the set value
29
Mix_valve_step_close_time 0
255
7
s
For each step the valve closes
1/2 of the set value
30
Mix_valve_interval_time 0
255
5
s
Mixing valve delay
31
Mixing_p_hyst
0
255
2
°C
Hysteresis for maximum valve opening
32
Mixing_still_hyst
0
255
2
°C
33
Power control mode
0
1
1
0 = Minimum number of burners
1 = Maximum number of burners
34
3° pump
0
1
0
0 = System/loop
1 = Low temperature circuit
35
Frost protection
-30
15
3
°C
System
36
Gas_type
1
7
1
1 = NG with flue < 15m
2 = NG with flue > 15m
3 = LPG with flue < 15m
4 = LPG with flue > 15m
37
T_out_min
-20
30
0
°C
38
T_out_max
0
30
18
°C
39
T_out_correct
-30
30
0
°C
40
T_emergency
10
80
70
°C
41
Parameter_reset
0
1
0
42
Flow switch on slave
0
1
1
0 = The slave does not control the pressure switch
43
Protocol
0
1
1
0 = Eco protocol
1 = Argus link (new)
CONDEXA PRO
59