CONDEXA PRO
32
Minimum
distance
10 mm
Minimum
distance
300 mm
Condensate collector
(at atmospheric pressure)
i > 3%
Mains
sewers
i
i
≥
3
°
PREPARING THE CONDENSATE DRAIN
The condensate produced by the boiler during normal
operation must be drained at atmospheric pressure and
must conform to any current standards and law applica-
ble.
- install a neutraliser where required by law.
b
Specific pipes for condensing boilers must be
used. For installation, follow the instructions
provided with the kit.
Drain trap along the drain pipe
If the vertical or horizontal section of the drain pipe
needs to be extended by more than 4 metres, a drain
trap must be installed at the foot of the pipe.
The useful height of the drain trap must be at least 300
mm. The discharge of the drain trap must then be con-
nected to the sewerage system.
Summary of Contents for CONDEXA PRO 100 S
Page 72: ...CONDEXA PRO 72...
Page 73: ...CONDEXA PRO 73...
Page 74: ...CONDEXA PRO 74...
Page 75: ...CONDEXA PRO 75...