Manual VIPA System 300V
Chapter 6 Analog Input Modules
HB130E - SM - Rev. 07/44
6-27
Measuring type 4wire Resistance measuring (
Measuring type coding: 0100b
)
Measuring range Range / Representation
Range
coding
150 Ohm
176.383 Ohm = End Overdrive region
(32511)
0...150 Ohm = Nominal range
( 0...27648)
negative values physically not possible
0010b
300 Ohm
352.767 Ohm = End Overdrive region
(32511)
0...300 Ohm = Nominal range
( 0...27648)
negative values physically not possible
0100b
600 Ohm
705.534 Ohm = End Overdrive region
(32511)
0...600 Ohm = Nominal range
( 0...27648)
negative values physically not possible
0110b
Measuring type 4wire Thermo resistance (
Measuring type coding: 1000b
)
Measuring range Range / Representation
Range
coding
Pt100
Standard
1000°C
= End Overdrive region
(10000)
- 200...850°C = Nominal range
(-2000...8500)
- 243°C
= End Underdrive region
(-2430)
(0.1°C/digit)
0010b
Pt100
Climate
155°C
= End Overdrive region
(15500)
- 120...130°C = Nominal range
(-12000...13000)
- 145°C
= End Underdrive region
(-14500)
(0.01°C/digit)
0000b
Pt 100
reference
junction
1000
= End Overdrive region
(10000)
-100...200
= Nominal range (-1000...2000)
-243
= End Underdrive region
(-2430)
(0.1°C/Digit)
1101b
2)
Ni100
Standard
295°C
= End Overdrive region
(2950)
- 60...250°C = Nominal range
(-600...2500)
- 105°C
= End Underdrive region
(-1050)
(0.1°C/digit)
0011b
1)
Ni100
Climate
295°C
= End Overdrive region
(29500)
- 60...250°C = Nominal range
(-6000...25000)
- 105°C
= End Underdrive region
(-10500)
(0.01°C/digit)
0001b
1)
Please use up to the firmware version V.1.2.6 of the analog module the coding 1011b.
The current firmware version may be found at the front flap beneath the label strip.
2)
The measuring range Pt100 reference junction is available starting with firmware version V. 1.3.8. Since
this measuring range is not supported by the Siemens SIMATIC manager, the parameterization only takes
place exclusively at run time.
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...