Chapter 5 Digital Input/Output Modules
Manual VIPA System 300V
5-8
HB130E - SM - Rev. 07/44
DC 24V
M
intern
Bus
Optocoupler
LED
Input module
DC 24V
LED
Output module
Bus
Optocoupler
M
intern
Module name
VIPA 323-1BL00
Dimensions and Weight
Dimensions WxHxD
40x125x120mm
Weight
210g
Data for specific module
Number of Inputs
16
Number of Outputs
16
Programming specifications
Input data
2Byte
Output data
2Byte
Voltages, Currents, Potentials
Rated load voltage L+
DC 24V
Isolation
- between channels and backplane bus
yes
Isolation tested with
DC 500V
Current consumption
- from the backplane bus
130mA
- from load voltage L+ (without load)
30mA
Power dissipation of the module
5.8W
Status, Interrupts, Diagnostics
Status display
green LED per channel
Group error display
red F-LED
Data for selecting a sensor
Input voltage
- Rated value
DC 24V
- for signal "1"
15 ... 28.8V
- for signal "0"
0 ... 5V
Input current
- for signal "1"
7mA
Input delay
- from "0" to "1"
3ms
- from "1" to "0"
3ms
Connection of 2-wire-BEROs
possible
- Permitted bias current
1.5mA
Data for selecting an actuator
Output voltage
- at signal "1"
DC 24V
Output current
- at signal "1"
Rated value
1A (max. 1.2A)
Lamp load max.
5W per group
Switch rate max.
- for resistive load
1kHz
- for inductive load (IEC 947-5-1, DC 13)
0.5Hz
- lamp load
1Hz
Limit of the inductive circuit interruption voltage
typ. L+ (-52V)
Schematic
diagram
Technical Data
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...