Chapter 6 Analog Input Modules
Manual VIPA System 300V
6-14
HB130E - SM - Rev. 07/44
331-1KF01 - AI 8x13Bit - Technical Data
Module name
VIPA 331-1KF01
Dimensions and Weight
Dimensions (WxHxD in mm)
40x125x120
Weight ca.
205g
Data for specific module
Number of inputs
8
- for 4wire resistance-type sensor
8
Length of cable
- shielded
200m / 50m at measuring range ±50mV
Programming specifications
Input data
8Words
Parameter data
14Byte
Diagnostic data
-
Voltages, Currents, Potentials
Constant current for resistance-type sensor
- resistance thermometer and
resistance measurement 0 ... 600
Ω
0.83mA
- resistance measurement 0 ... 6k
Ω
0.25mA
Isolation
- between channels and backplane bus
yes
- between the channels
no
Permitted potential difference
- between the inputs (U
CM
) DC
2V
- between the inputs and M
INTERN
(U
ISO
)
DC 75V / AC 60V
Isolation tested with
DC 500V
Current consumption
- from the backplane bus
200mA
Power dissipation of the module
1.0W
Analog value generation
Measuring principle
Sigma delta
Integration time / conversion time / resolution
(per channel)
-
programmable
yes
- Integration time in ms
60ms
50ms
- Basic conversion time in ms
61ms
51ms
additional conversion time for
measuring resistance in ms
61ms 51ms
- Resolution incl. overrange
13Bit
continued ...
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...