Manual VIPA System 300V
Chapter 6 Analog Input Modules
HB130E - SM - Rev. 07/44
6-25
At the parameterization, a parameter area of 16Byte length is stored in the
record sets 0 and 1. Here the data irrelevant for the module AI 2x12Bit
(331-7KB01) are ignored.
Using the SFCs 55, 56 and 57 you can only change parameters at record
set 1 and transfer during runtime to the analog module. On this way
parameters may be transferred which are not supported by the Siemens
SIMATIC manager, as e.g. setting of high temperature measuring ranges.
Record set 0 (Byte 0 to 1):
Byte Bit 7 ... Bit 0
Default
0
Group diagnosis bit coded
Bit 0: Channel 0/1
Bit 1: Channel 2/3
Bit 2: Channel 4/5
Bit 3: Channel 6/7
Bit 7 ... 4: reserved
00h
1
Wire break test bit coded
Bit 0: Channel 0/1
Bit 1: Channel 2/3
Bit 2: Channel 4/5
Bit 3: Channel 6/7
Bit 7 ... 4: reserved
00h
Record set 1 (Byte 0 to 13):
Byte Bit 7 ... Bit 0
Default
0
Bit 5 ... 0: reserved
Bit 6: Diagnostic interrupt release
Bit 7: Process interrupt release
00h
1
Interference frequency suppression
Bit 0, 1: Channel 0/1
Bit 2, 3: Channel 2/3
Bit 4, 5: Channel 4/5
Bit 6, 7: Channel 6/7
AAh
2
Mode Channel 0/1
Bit 3 ... 0: Measuring range
Bit 7 ... 4: Measuring type
19h
(+/-10V)
3
Mode Channel 2/3
Bit 3 ... 0: Measuring range
Bit 7 ... 4: Measuring type
19h
(+/-10V)
4
Mode Channel 4/5
Bit 3 ... 0: Measuring range
Bit 7 ... 4: Measuring type
19h
(+/-10V)
5
Mode Channel 6/7
Bit 3 ... 0: Measuring range
Bit 7 ... 4: Measuring type
19h
(+/-10V)
6, 7
Upper limit value Channel 0
7FFFh
8, 9
Lower limit value Channel 0
8000h
10, 11 Upper limit value Channel 2
7FFFh
12, 13 Lower limit value Channel 2
8000h
Note for deactivating a channel group!
With the Coding 0000 0000 a channel group may be deactivated.
Structure of the
parameter bytes
Record set 0,
Record set 1
Parameter
Record set 0
(not parameterizable
via SFC)
Parameter
Record set 1
(parameterizable
via SFC)
00: 400Hz (2.5ms)
01: 60Hz (16.6ms)
10: 50Hz (20ms)
11: 10Hz (100ms)
7
0 Bit-No.
Byte 2 ...9
Coding for
measuring type
Coding for
measuring range
4
3
For the according coding of mea-
suring range and measuring type
see "Modus per channel" at the
following pages.
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...