Chapter 6 Analog Input Modules
Manual VIPA System 300V
6-32
HB130E - SM - Rev. 07/44
Message
Possible error cause
Remedial
Project
engineering/
Parameterization
error
Parameterization at run
time:
Wrong function code in
record set
Proof the parameteri-
zation during run time
Wire break
Sensor allocation is too
high-impedance
install another sensor
type or cable with a
higher cross-section
Interruption of the conductor
between module and sensor
Install conductor
connection
Channel is not wired (open) Deactivate the channel
group (parameter
measuring type)
Wire the channel
Measuring range
underflow
Input value is under the
underdrive region, error
causes may be:
•
at measuring range
4 ... 20mA, 1 ... 5V
- sensor connection
polarity inversion
- wrong measuring range
•
other measuring ranges
- wrong measuring range
Check connections
Parameterize another
measuring range
Parameterize another
measuring range
Measuring range
overflow
Input value higher than
overdrive region
Parameterize another
measuring range
Process interrupt
lost
During the processing of a
process interrupt in OB40, a
new process interrupt with
the same error cause
occurs.
Failure of the
external power
supply
Connection of the external
power supply forgotten
Power supply failure
Cable defect res. not
correctly connected
Supply the module with
external DC 24V
Control external power
supply and change it
Control cable res.
replace it
Common mode
Different potentials between
grounds >3V or wire break
at ground
Remove wire break,
lower potential
difference
Error cause
and remedy
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...