Manual VIPA System 300V
Chapter 6 Analog Input Modules
HB130E - SM - Rev. 07/44
6-23
The analog values are only processed by the CPU in binary representation.
Hereby the process signals are transformed into digital format in the analog
module and passed on to the CPU as word variable.
The digitized analog value is the same for input and output values at the
same nominal range.
The resolution of an analog value is 14 Bit plus sign Bit. Bit 15 serves as
sign bit (SG) with the meaning:
Bit 15 = "0"
→
positive value
Bit 15 = "1"
→
negative value
Depending upon parameterized interference frequency (integration time)
the modules offers different resolutions. The not used low byte bits are set
to "0".
Resolution
Analog value
High-Byte
Low-Byte
Bit
number 15
14 13 12 11
10 9 8 7 6 5 4 3 2 1 0
Value
SG 2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
14Bit + sign SG Measuring value (interference frequency 10Hz)
0
12Bit + sign SG Measuring value (interference frequency 50, 60Hz)
0
0
0
9Bit + sign
SG Measuring value
(interference frequency 400Hz)
0
0
0
0
0
0
Note!
This resolution does not apply to temperature levels. The converted
temperature levels are the result of a conversion of the analog module.
As soon as a measured value exceeds the overdrive region and/or falls
below the underdrive region, the following value is issued:
Measuring value > end of overdrive region:
32767 (7FFFh)
Measuring value < end of underdrive region:
-32768 (8000h)
Analog value
representation
Resolution
Behavior at over-
and underflow
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...