Manual VIPA System 300V
Chapter 6 Analog Input Modules
HB130E - SM - Rev. 07/44
6-31
Byte 0 to 15:
The record set 1 contains the 4Byte of record set 0 and additionally 12Byte
module specific diagnostic data.
The diagnostic bytes have the following assignment:
Record set 1 (Byte 0 to 15):
Byte
Bit 7 ... Bit 0
Default
0 ... 3 Content record set 0 (see page before)
-
4
Bit 6 ... 0: Channel type
70h:
Digital
input
71h:
Analog
input
72h:
Digital
output
73h:
Analog
output
74h:
Analog
in-/output
Bit 7: More channel types present
0:
no
1: yes
71h
5
Bit 7 ... 0: Number of diagnostic bits, that the module
throws per channel
08h
6
Bit 7 ... 0: Number of similar channels of a module
04h
7
Bit 0: Channel error Channel 0
...
Bit 7: Channel error Channel 7
00h
8
Bit 0: Project engineering/Parameterization error
Channel
0
Bit 1: Common mode error
Bit 3 ... 2: reserved
Bit 4: Wire break Channel 0
Bit 5: reserved
Bit 6: Underflow Channel 0
Bit 7: Overflow Channel 0
00h
... ...
15
Bit 0: Project engineering/Parameterization error
Channel
7
Bit 1: Common mode error
Bit 3 ... 2: reserved
Bit 4: Wire break Channel 7
Bit 5: reserved
Bit 6: Underflow Channel 7
Bit 7: Overflow Channel 7
00h
Note!
Please note that the AI 2x12Bit (331-7KB01) exclusively supplies
diagnostic data of the channel group 0/1!
Diagnostics
record set 1
Summary of Contents for HB130E SM
Page 1: ...Manual VIPA System 300V SM Order no VIPA HB130E_SM Rev 07 44...
Page 2: ...Lerrzeichen...
Page 6: ...Contents Manual VIPA System 300V ii HB130E SM Rev 07 44...
Page 14: ...Chapter 1 Basics Manual VIPA System 300V 1 6 HB130E SM Rev 07 44...
Page 58: ...Chapter 4 Digital Output Modules Manual VIPA System 300V 4 24 HB130E SM Rev 07 44...
Page 128: ...Index Manual VIPA System 300V A 2 HB130E SM Rev 07 44 M Stich...