Coding in the delivered condition
Possible change
A9:7
*
1
With pump idle time:
Heating circuit pump
OFF in case the set
value is changed (by
changing the operating
mode or the set room
temperature)
A9:0
*
1
Without pump idle time
A9:1
to
A9:15
With pump idle time, ad-
justable from 1 to 15
b0:0
*
1
With remote control:
Heating mode/reduced
mode: weather-com-
pensated
*
2
b0:1
Heating mode: weather-
compensated
Reduced mode: with
room temperature hook-
up
b0:2
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
b0:3
Heating mode/reduced
mode: with room tem-
perature hook-up
b2:8
With remote control unit
and for the heating cir-
cuit, heating with room
temperature hook-up
must be encoded:
Room influencing factor
8
*
2
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
*
1
With remote control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
tion
*
2
b5:1
to
b5:8
Heating circuit pump
logic function; see the fol-
lowing table
Parameter ad-
dress b5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
1:
enabled RT
actual
> RT
set
+ 5 K; disabled RT
actual
< RT
set
+ 4 K
2:
enabled RT
actual
> RT
set
+ 4 K; disabled RT
actual
< RT
set
+ 3 K
Code 2
(cont.)
56
Coding
5692
569
GB
*1
Only for weather-compensated control units.
*2
Change the code for the heating circuit without mixer A1 or for the mixer circuit M2 only,
if the remote control unit affects that heating circuit.
Summary of Contents for Vitodens 300
Page 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Page 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Page 127: ...127 5692 569 GB...