Function area
Coding addresses
System design
00
Boiler/burner
06 to 54
Domestic hot water
56 to 73
General
76 to 9F
Boiler circuit (heating circuit A1 without
mixer)
A0 to Fb
Mixer circuit (heating circuit M2 with mixer) A0 to Fb
Note
Codes, which are irrelevant (due to the system equipment level or the setting of
other codes) will not be displayed.
For heating systems with one heating circuit without mixer and one heating cir-
cuit with mixer, initially the available coding addresses A0 to Fb are scrolled for
the heating circuit without mixer A1, then those for the heating circuit with mixer
M2.
Coding
Coding in the delivered condition
Possible change
System designs
00 :1
System design 1:
1 heating circuit without
mixer A1, without DHW
heating
00 :2
System design 1, 6:
1 heating circuit without
mixer A1, with DHW heat-
ing
00 :3
System design 5:
1 mixer circuit M2, with-
out DHW heating
00 :4
System design 5:
1 mixer circuit M2, with
DHW heating
00 :5
System design 2, 3, 4:
1 heating circuit without
mixer A1, 1 mixer circuit
M2 without DHW heating
00 :6
System design 2, 3, 4:
1 heating circuit without
mixer A1 and 1 mixer cir-
cuit M2, with DHW heat-
ing
Code 2
(cont.)
43
Coding
5692
569
GB
Summary of Contents for Vitodens 300
Page 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Page 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Page 127: ...127 5692 569 GB...