Checking the boiler water temperature sensor, cylinder tem-
perature sensor or the flow temperature sensor of the low
loss header
1.
Boiler water temperature sensor:
Pull the leads off boiler temperature
sensor
A
and check the resis-
tance.
Cylinder temperature sensor: Pull
plug
%
from the cable harness on
the control unit and check the resis-
tance.
Flow temperature sensor: Pull plug
"X3" from the control unit and check
the resistance across terminals
"X3.4" and "X3.5".